Energy Action helps Australian businesses take a broader approach to energy management, including electricity procurement, contract optimisation and strategies for controlling energy costs. Working with experienced energy specialists can help your organisation understand its energy profile and identify opportunities that offer genuine commercial value.
Estimated Reading Time: 10 minutes
Electricity costs are not always determined solely by how many kilowatt-hours your business consumes. For many Australian commercial and industrial sites, the way electrical equipment draws power can also influence network demand charges and overall energy costs.
This is where power factor correction business strategies become important.
Power factor measures how effectively an electrical installation converts supplied power into useful work. A high power factor means the available electrical capacity is being used efficiently. In contrast, poor power factor means more apparent power must flow through the electrical system to provide the same useful output.
For businesses operating motors, pumps, compressors, refrigeration, air-conditioning and industrial machinery, poor power factor can increase demand and consume valuable electrical capacity.
However, power factor correction is not automatically worthwhile for every site. Its financial value depends heavily on the electricity tariff, demand profile and existing power factor. Therefore, businesses should understand the problem before investing in correction equipment.
To understand power factor, it helps to separate electricity into three measurements.
| Measurement | Meaning | Unit |
| Real power | Power that performs useful work | kW |
| Reactive power | Power supporting electromagnetic fields | kVAr |
| Apparent power | Total electrical capacity required | kVA |
Power factor represents the relationship between real power and apparent power:
Power factor = kW ÷ kVA
For example, a business requiring 100 kW while drawing 125 kVA has a power factor of:
100 ÷ 125 = 0.80
If that same 100 kW load operates at a power factor of 0.95, apparent demand falls to approximately 105 kVA.
The useful work has not changed. However, the electrical system needs to carry considerably less apparent power.
The effect becomes clearer when comparing different power factors.
| Useful load | Power factor | Apparent demand |
| 100 kW | 1.00 | 100 kVA |
| 100 kW | 0.95 | 105 kVA |
| 100 kW | 0.90 | 111 kVA |
| 100 kW | 0.80 | 125 kVA |
| 100 kW | 0.70 | 143 kVA |
At a power factor of 0.80, a 100 kW load requires 125 kVA. At 0.95, it requires only about 105 kVA.
Therefore, businesses charged according to kVA demand can have a strong financial reason to improve poor power factor.
Inductive electrical loads are common contributors to poor power factor because they require reactive power to establish electromagnetic fields.
Common examples include:
The impact depends on equipment size, design, operating hours and loading.
For example, an oversized motor may operate well below its rated capacity for much of the day. Under some conditions, lightly loaded motors can contribute to poor overall power factor.
Consequently, businesses should assess equipment under real operating conditions rather than relying only on equipment specifications.
Poor power factor does not necessarily mean that your business is consuming dramatically more kWh.
Instead, one of the main commercial problems is increased apparent demand.
Consider a manufacturing site with a peak useful load of 500 kW.
At 0.80 power factor:
500 ÷ 0.80 = 625 kVA
At 0.95 power factor:
500 ÷ 0.95 = approximately 526 kVA
That represents a difference of around 99 kVA.
If the network tariff calculates demand charges using kVA, the difference can translate directly into higher electricity costs.
This is why understanding demand charges is important when reviewing business energy costs. Energy Action's existing guidance also highlights demand charges and peak usage as important considerations when evaluating electricity supply contracts.
Higher apparent power also requires more current to travel through electrical infrastructure.
As a result, cables, transformers and switchboards can carry additional current without producing additional useful output.
For a growing business, this can become an important operational issue. If electrical infrastructure is approaching its capacity, improving power factor may release capacity for new machinery or expanding operations.
Therefore, the business case for correction can involve more than electricity bill savings.
Power factor correction compensates for reactive power so less reactive power needs to come from the upstream electrical network.
Capacitors are commonly used for this purpose. They supply reactive compensation closer to the equipment requiring it, thereby reducing apparent power and current upstream.
Businesses can use several configurations.
| Correction type | How it works | Suitable situation |
| Individual | Installed near specific equipment | Large, predictable motor loads |
| Group | Corrects several related loads | Equipment operating together |
| Central | Corrects loads from one central location | Facilities with multiple loads |
| Automatic | Switches capacitor stages as demand changes | Sites with variable loads |
Automatic power factor correction is particularly useful for businesses where equipment loads change throughout the day.
However, correction equipment needs proper engineering. Oversizing, harmonics and inappropriate switching can create additional electrical problems.
The actual financial impact varies considerably because Australian network tariffs and business load profiles differ.
Consider a hypothetical facility operating at 400 kW.
| Item | Before correction | After correction |
| Useful demand | 400 kW | 400 kW |
| Power factor | 0.80 | 0.95 |
| Apparent demand | 500 kVA | 421 kVA |
| Difference | 79 kVA |
The useful load remains unchanged, yet apparent demand falls by approximately 79 kVA.
If the applicable demand component were hypothetically $15 per kVA per month and the full reduction affected billable demand:
79 kVA × $15 × 12 = $14,220 annually
This figure is only an illustration. Actual savings depend on network tariffs, maximum-demand calculations, operating conditions and other contractual factors.
Therefore, businesses should use their actual meter and tariff data before estimating returns.
For businesses with kVA-based tariffs, reducing apparent demand can lower network demand charges. This can provide an ongoing saving without changing productive output.
Improving power factor reduces current for a given useful load. Consequently, existing cables, transformers and switchgear may have more capacity available.
This can be particularly valuable for businesses planning additional equipment or electrification projects.
Electrical losses increase with current. Therefore, reducing unnecessary current can lower some losses within the site's electrical distribution system.
However, businesses should not assume this will create a dramatic reduction in billed kWh.
Investigating power factor can reveal other opportunities involving motor loading, peak demand, equipment scheduling and overall efficiency.
Energy Action's existing business energy guidance includes power factor correction among efficiency measures businesses can consider alongside smart metering, efficient HVAC and other improvements.
Although closely related, power factor correction and energy efficiency are different.
| Power factor correction | Energy efficiency |
| Addresses reactive power | Reduces energy required for useful output |
| Can reduce kVA demand | Can reduce kWh consumption |
| Can lower electrical current | Reduces energy waste |
| Savings depend strongly on tariff | Savings relate more directly to consumption |
| Does not necessarily reduce useful load | Improves output per unit of energy |
For example, replacing an inefficient motor can reduce the electricity consumed to perform the same work. Power factor correction primarily improves how electrical capacity is used.
Therefore, businesses should investigate both opportunities rather than treating them as interchangeable.
The first step is reviewing electricity bills and tariff information.
Look for terms including:
If demand charges are based on kVA, power factor deserves closer investigation.
Next, review interval meter data. This can reveal when maximum demand occurs and whether power factor changes as different equipment operates.
Finally, consider a detailed electrical assessment. An assessment can measure power factor, kW, kVA, reactive power, current, voltage and harmonics under representative operating conditions.
Combining this technical information with tariff data allows the business to calculate whether correction is financially worthwhile.
A low power factor does not automatically justify installing correction equipment.
A stronger business case generally exists when:
If your tariff calculates demand exclusively in kW, the direct financial benefit from reducing kVA may be limited.
Therefore, tariff analysis should come before purchasing equipment.
Businesses can begin with a straightforward calculation:
Annual benefit = demand-charge savings + other measurable savings
Then:
Simple payback = installed cost ÷ annual benefit
For example, if a $24,000 system delivers verified annual savings of $8,000, the simple payback is three years.
However, a complete assessment should also consider maintenance costs, equipment life, future tariffs, load growth and changes to business operations.
Most importantly, calculate savings from actual operating data rather than a single power factor measurement.
Power factor correction works best as part of a wider demand management strategy.
Businesses can combine it with:
For example, power factor correction may reduce kVA during a production peak, while operational scheduling prevents several large machines starting simultaneously.
Together, these measures can provide greater savings than treating each energy issue separately.
A structured assessment can help prevent unnecessary investment.
First, collect 12 months of electricity bills and interval data. Determine whether maximum demand is measured in kW or kVA.
Second, measure power factor under normal operating conditions. If the site's loads vary, measurements should cover different production periods.
Third, identify the equipment contributing most to reactive demand.
Next, model the expected reduction in kVA after correction and apply your actual tariff to calculate potential savings.
Finally, compare installation and maintenance costs with expected savings and operational benefits.
This process transforms power factor correction from a technical purchase into an evidence-based business investment.
Poor power factor can create unnecessary costs for Australian businesses, particularly where network demand charges are calculated using kVA. It can increase apparent demand, consume electrical capacity and require infrastructure to carry more current than necessary.
However, power factor correction business investment should start with accurate data rather than assumptions.
Review your tariff, analyse interval data and measure actual power factor before investing. Then calculate how a proposed improvement would affect your demand charges and electrical capacity.
Energy Action helps Australian businesses take a broader approach to energy management, including electricity procurement, contract optimisation and strategies for controlling energy costs. Working with experienced energy specialists can help your organisation understand its energy profile and identify opportunities that offer genuine commercial value.
Visit Energy Action to explore smarter ways to manage business electricity costs and strengthen your long-term energy strategy.
Power factor correction compensates for reactive power so electrical infrastructure can deliver useful power more effectively. Capacitors or automatic capacitor banks commonly provide the correction. For businesses charged on kVA demand, improving power factor may reduce demand charges and improve available electrical capacity.
Power factor correction does not necessarily produce a significant reduction in kWh consumption because its primary purpose is to reduce reactive and apparent power. Instead, the main financial benefit often comes from reducing kVA demand. Some electrical losses may also decrease because less current flows through the site's infrastructure.
Check whether your electricity tariff includes kVA-based demand charges and review your power factor data. Interval meter information can show when maximum demand occurs, while an electrical assessment can identify the equipment contributing to poor power factor. Combining this information with tariff data provides a reliable estimate of potential savings.
Motors, compressors, pumps, refrigeration systems, HVAC equipment, transformers and other inductive machinery can contribute to poor power factor. However, the impact varies depending on equipment design and loading. Therefore, businesses should measure actual operating conditions before investing in correction equipment.
No. Power factor correction is generally more attractive where power factor is poor and electricity demand charges are calculated using kVA. Businesses with already strong power factor or tariffs based solely on kW may see much smaller direct savings. A site-specific tariff and electrical assessment is therefore essential before making an investment decision.